Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/21/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/19/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/19/2013 | ELECTRIC - FINAL | Denied | SMOKE ALARMS STILL NOT PROPERLY INSTALLED. ADD RE-FEE TO THIS PERMIT | |
| 06/13/2013 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/29/2013 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/29/2013 | ELECTRIC - FINAL | Not ready for Inspection | 1. BARE WIRING ON INTERIOR AND EXTERIOR EXPOSED 2. SMOKE ALARMS MISSING THROUGH OUT. (BEDROOMS & HALLWAY) 3. PLUG & SWITCH PLATES MISSING, OUTLETS FULL OF PAINT 4. MAIN POWER LINE TO PANEL (METER) FROM POLE NOT PROPERLY SUPPORTED CONSULT T.E.P. POWER LINE IS 6' A.G. 5. THIS AN UNGROUNED SYSTEM, ALL GROUNED OUTLETS ARE TO BE REMOVED AND REPLACED WITH UNGROUNDED EXCEPT GFC |
|
| 05/22/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
| 05/22/2013 | ELECTRIC - FINAL | Denied | HOME LOCKED - NO MSG - RESCH INSPECTION |