Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - RECONNECT
Permit Number - T13CM03070
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Denied
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/30/2013 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
05/30/2013 | ELECTRIC - RECONNECT | Denied | 1. BARE WIRES HANDING OUT OF BROKEN PORCH LIGHT 2. BREAKER COVER AT METER MISSING 3. PROVIDE MINIMUM 3' CLEARANCE IN FRONT OF PANEL (UNABLE TO OPEN PANEL) 4. WIRING HANGING OUT OF CEILING 5. SMOKE ALARMS REQUIRED IN BEDROOMS AND AREAS LEADING TO BEDROOMS. ALARMS TO BE MINIMUM 3' FROM SUPPLY AIR 6. DEAD FRONT MISSING FROM EXTERIOR PANEL 7. PROVIDE COVER OVER EXPOSED ROMEX AT INTERIOR PANEL (SHEET ROCK) |