Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/06/2013 | ELECTRIC - FINAL | Partial Approval | 1 BOND GAS & WATER LINES 2 RELOCATE SMOKE ALARMS WITHIN 36" FORCED AIR REGISTERS 3 ALL ADDITIONS SHOULD BE ON RECORD NOTES 1-2 RECAL 2090 |
|
| 05/21/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/21/2013 | ELECTRIC - FINAL | Denied | THE GROUNDING ELECTRODE SYSTEM HAS BEEN VANDALIZED. PROVIDE 2 GROUND RODS MIN 6' APART & RECONNECT GROUNDING CONDUCTORS & PROVIDE ELEC & GAS BOND. PROVIDE A LIGHT FIXTURE OR COVER PLATE AT BACK PORCH. THE ROMEX TO THE RECEPTACLE IN LAUNDRY ROOM MUST BE PROTECTED FROM PHYSICAL DAMAGE OR REMOVE. THE RECEPTACLE FOR THE COOLER NEEDS A BUBBLE TYPE WATERTIGHT COVER. PROVIDE GLOBES OVER LIGHT BULBS IN CLOSETS. THE SUBPANEL IN CLOSET IS LOOSE, RE-SECURE TO WALL. |