Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/02/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 06/27/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 06/27/2013 | ELECTRIC - FINAL | Denied | 1. GROUNDING ELECTRODE MISSING ON SEPARATE BUILDING 250.32 2. SUBPANEL NEUTRALS & GROUNDS TO BE SEPARATED: 250.24, 250.92, 250.94, 408.40, & 250.28 |