Inspection History Details
Inspection Status: Denied
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/28/2013 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/28/2013 | MECHANICAL - FINAL | Denied | SECURE WATER HEATER VENT W/ SCREWS AT EACH JOINT PLUG ABANDON GAS LINE CORRECT WH RELIEF VALVE - MAY NOT BE TRAPPED AND REQUIRES HARD PIPE SEAL SCREW INTO ROOF PENETRATIONS AT BREAKER BOX SECURE FRONT & BACK SIDES OF FLASHING AT CONDENSATE PENETRATION |
|
| 05/21/2013 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* | |
| 05/21/2013 | MECHANICAL - FINAL | Partial Approval | STILL NEED TO REINSTALL WH AND ELIMINATE ABANDON FURNACE VENT. CAP OFF GAS. CORRECT CONDENSATE RESTRICTION & TERMINATION |