Permit: T13CM02904

Parcel: 12611020A


Addresses:

4349 E BROADWAY BL

Inspection Status: Approved

Inspection History: BUILDING - FINAL

Date Description Inspector Results Comments
08/22/2017 BUILDING - FINAL Approved
08/21/2017 BUILDING - FINAL Denied 1- SHALL PROVIDE AN EXPANSION TANK FOR THE WATER HEATER.
2- SHALL PROVIDE A VACUUM RELIEF VALVE ON THE COLD WATER SUPPLY TO THE WATER HEATER.
3- SHALL PROVIDE A DRAIN FOR THE WATER HEATER DRAIN PAN.
4- SHALL PROVIDE AN OPEN FRONT SEAT AT WATER CLOSET.
5- SHALL PROVIDE A MIRROR FOR THE LAVATORY LOCATED 40 INCHES TO THE REFLECTION FROM FINISH FLOOR.
6- SHALL PROVIDE FRESH BACKUP BATTERIES FOR THE EMERGENCY LIGHTING.
7- SHALL PROVIDE A LOCK OUT TAG OUT CLIP ON THE WATER HEATER DEDICATED CIRCUIT BREAKER.
8- SHALL PROVIDE A CIRCUIT BREAKER SCHEDULE AT SERVICE PANEL.