Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T13CM02815
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/14/2013 | FIRE SPKLR - FINAL | Approved | ||
10/07/2013 | FIRE SPKLR - FINAL | Denied | 1. Some of the uprights in the dining area to close to the sprayed on foam need to keep a 1 inch plane clear from all spinkler heads. 2. Need to add sprinkler coverage under roll up door in the dinning area x3. |