Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/12/2013 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 06/12/2013 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* | |
| 06/12/2013 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | 1. MAX BREAKER SIZE FOR 14 GA WIRE IS 15 AMP 2. SERVICE OUTLET FROM PANEL MISSING PROTECTIVE COVER 3. PANEL COVER NOT PROPERLY INSTALLED 4. IF USING EXISTING DISCONNECT AS A J-BOX, PROVIDE LOCK, SCREWS, OR OTHER MEANS TO SECURE ACCESS 5. PROVIDE GUYED WIRES ON MASTS (RISER) OVER 24" IN HEIGHT |