Permit: T13CM02803

Parcel: 14023057D


Addresses:

814 E DREXEL RD


Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Permit Number - T13CM02803

Inspection Description - ELECTRIC - SERVICE UPGRADE

Inspection Status - Approved

Date Description Inspector Results Comments
07/12/2013 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/12/2013 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
06/12/2013 ELECTRIC - SERVICE UPGRADE Not ready for Inspection 1. MAX BREAKER SIZE FOR 14 GA WIRE IS 15 AMP
2. SERVICE OUTLET FROM PANEL MISSING PROTECTIVE COVER
3. PANEL COVER NOT PROPERLY INSTALLED
4. IF USING EXISTING DISCONNECT AS A J-BOX, PROVIDE LOCK, SCREWS, OR OTHER MEANS TO SECURE ACCESS
5. PROVIDE GUYED WIRES ON MASTS (RISER) OVER 24" IN HEIGHT