Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/08/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/05/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/05/2013 | ELECTRIC - FINAL | Denied | SMOKE DETECTOR MISSING IN HALL. NOTE #'S 3, 5, 8, 11, NOT ADDRESSED. WATER HEATER MISSING | |
| 05/08/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/08/2013 | ELECTRIC - FINAL | Denied | 1. 60 AMP 2 POLE BREAKER MISSING HANDLE TIE, WRONG MANUFACTURE, AND DAMAGED 2. WIRING ON REAR PORCH NOT CODE COMPLIANT - EXTENTION CORD WIRING 3. PLEASE VERIFY PERMITS FOR WORK DONE IN LAUNDRY ROOM/OLD CARPORT - NEW PLUMBING, ELECTRIC DEVICES HANGING OUT OF WALLS, BOXES TOO FAR BACK FROM SURFACES 4. EXPOSED CONDUCTORS 5. RE-INSTALL BOXES INTO WALL 6. REPLACED KITCHEN RECEPTACLES TO BE GFCI PROTECTED 7. NEED COVER HARDWARE SUBPANEL 8. DOORBELL TRANSFORMER POWER NEED BOX 9. HALL SMOKE DETECTOR BROKEN - BEDROOM IN WRONG LOCATION 10. BACK BATH GFCI INSTALLED NOT CODE COMPLIANT - ZIP CORD WIRING 11. GROUNDED RECEPTACLES ON NON-GROUNDED CIRCUITS 12. T & P VALVE DISCHARGING TO ROOF |