Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/21/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/21/2013 | ELECTRIC - FINAL | Denied | SEE NOTES LAST INSP 5-17-13 NO RISER CONDUCTORS |
|
| 05/17/2013 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 05/17/2013 | ELECTRIC - FINAL | Not ready for Inspection | 1. PROVIDE #4 GROUND WIRE TO TWO GROUND RODS, ROD SPACING MIN. 6' WATER AND GAS ARE TO BE BONDED 2. PROVIDE TWO POINTS OF CONNECTION (STRAP) TO BUILDING AT RISER 3. MAST OVER 24" ARE TO HAVE GUYED (?) WIRE SUPPORTS |