Permit: T13CM02624

Parcel: 118050890


Addresses:

1846 W SAN JUAN TR

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
10/03/2013 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
10/01/2013 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/01/2013 ELECTRIC - SERVICE UPGRADE Denied REMOVE #4 BARE IN RISER CONDUIT
05/30/2013 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/30/2013 ELECTRIC - SERVICE UPGRADE Denied 1. 1 #4 WIRE PER CLAMP - 110-26 NEC NO SPLICES ON GEC UNLESS IRREVERSIBLE 250 NEC.
2. PROVIDE FULL SIZE NEUTRAL WITH WHITE I.D. OR LOAD CALC'S FOR REDUCED SIZED NEU RISER
3. #4 BARETO GROUND ROD TO SHORT. STRAP ALL #4 TO STRUCTURE.
4. USE APPROVED CLAMP FOR COND ENTERING ENCLOSURE. 1/4" CABLE SHEAT INSIDE. USE QUALIFIED ELECTRICIAN INSIDE
05/21/2013 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/17/2013 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*