Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - SERVICE UPGRADE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/03/2013 | ELECTRIC - SERVICE UPGRADE | Approved | IVRS - Inspection :* | |
| 10/01/2013 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 10/01/2013 | ELECTRIC - SERVICE UPGRADE | Denied | REMOVE #4 BARE IN RISER CONDUIT | |
| 05/30/2013 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/30/2013 | ELECTRIC - SERVICE UPGRADE | Denied | 1. 1 #4 WIRE PER CLAMP - 110-26 NEC NO SPLICES ON GEC UNLESS IRREVERSIBLE 250 NEC. 2. PROVIDE FULL SIZE NEUTRAL WITH WHITE I.D. OR LOAD CALC'S FOR REDUCED SIZED NEU RISER 3. #4 BARETO GROUND ROD TO SHORT. STRAP ALL #4 TO STRUCTURE. 4. USE APPROVED CLAMP FOR COND ENTERING ENCLOSURE. 1/4" CABLE SHEAT INSIDE. USE QUALIFIED ELECTRICIAN INSIDE |
|
| 05/21/2013 | ELECTRIC - SERVICE UPGRADE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/17/2013 | ELECTRIC - SERVICE UPGRADE | Not ready for Inspection | IVRS - Inspection :* |