Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2013 | ELECTRIC - FINAL | Partial Approval | 1. DEAD FRONT STILL NOT INSTALLED 2. SERAL TITE TO AC NOT PROPERLY STRAPPED 3. CORRECTIONS TO BE MADE WITHIN 7 DAYS |
|
| 05/07/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 05/02/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/02/2013 | ELECTRIC - FINAL | Denied | 1) INSULATE EXPOSED HOT CONDUCTOR INTO MAIN BREAKER. 2) CANNOT TAP INTO MAIN LUGS, ALSO CANNOT DBL LUG CONDUCTORS. TAPE WITH WIRES USED AS HOT. 3) DEADFRONT COVER MISSING, PLUG UNUSED OPENINGS IN SERVICE PANEL |