Permit: T13CM02495

Parcel: 12517039A


Addresses:

3837 E BROADWAY BL


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T13CM02495

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
08/22/2013 FIRE - FINAL Approved
08/19/2013 FIRE - FINAL Denied 1. Panic hardware needed on both rear egress doors and remove any other locking devices on doors omly panic hardware allowed.
2. Post occupant load sign by main egress door 2" inch high letters with OCC LOAD 90 as per approved plans.
3. Need to mount fire extinguishers 1 for every 1500 sq. ft. of building space, size 2A - 10BC with a travel distance of no more than 75 feet.
4. Hood testing failed piping not working to 4 nozzles
5. Need to check nozzles over griddle to low do not meet the min requirement in height.
6. Need to start test all over again for the hood extinguisher system.