Permit: T13CM02423

Parcel: 120051180


Addresses:

848 W OHIO ST

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
05/15/2013 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
05/02/2013 ELECTRIC - SERVICE UPGRADE Partial Approval IVRS - Inspection :*
04/26/2013 ELECTRIC - SERVICE UPGRADE Not ready for Inspection IVRS - Inspection :*
04/26/2013 ELECTRIC - SERVICE UPGRADE Not ready for Inspection 1) MASTHEAD OVER 24" FROM ROOF MUST HAVE APPROVED GUY WIRES
2) REMOVE ALL PAINT FROM WATER AND GAS PIPING WHERE BONDING CLAMPS ARE TO ATTACH
3) PLUG ALL OPEN K.O.'S IN BOTTOM OF PANEL