Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/08/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/07/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 05/07/2013 | ELECTRIC - FINAL | Approved | 1. SHEET METAL THREAD SCREWS NOT ALLOWED FOR GROUNDING 250.8 2. FILL ALL UNUSED OPENINGS WITH APPROVED PARTS 3. NEED PERMANENT METAL ADDRESS LABEL 4. BOND BOTH ENDS OF METAL RACE WAY FOR GROUNDING ELECTRODE CONDUCTOR 250.64 5. LAND ALL STRANDS UNDER TERMINALS 6. SUPPORT RISER BELOW PANEL - 1/4" MINIMUM HARDWARE 7. NEED GAS & WATER BOND |