Permit: T13CM02392

Parcel: 110113610


Addresses:

2480 N SWAN RD


Inspection Status: Approved

Inspection History: BUILDING - FINAL

Permit Number - T13CM02392

Inspection Description - BUILDING - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/27/2014 BUILDING - FINAL Approved IVRS - Inspection :*
02/26/2014 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
02/26/2014 BUILDING - FINAL Not ready for Inspection CONNECT SANITATION UNIT TO WATER LINE SHOWN ON PLANS W/ APPROVED TUBING. RP TEST IS OK. AIR CAPS AT ALL INDIRECT DRAINS; ICE MACHINE, CASE DRAINS
02/25/2014 BUILDING - FINAL Cancelled IVRS - RI canceled
01/31/2014 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
01/31/2014 BUILDING - FINAL Not ready for Inspection FS CORRECTION OK. INSTALL DOME STRAINER. CONNECT STERILIZER IN PRODUCE TO RPA, FOLLOW ALL INSTALL INSTRUCTIONS. PROVIDE TEST REPORTS FOR BACKFLOW ASSEMBLIES. COMPLETE OTHER NOTED CORRECTIONS AND PLAN REQUIREMENTS. PROVIDE WATER PIPING STERILIZATION DOCUMENTATION.
12/12/2013 BUILDING - FINAL Not ready for Inspection IVRS - Inspection :*
12/12/2013 BUILDING - FINAL Not ready for Inspection COMPLETE ALL NOTED CORRECTIONS. PROVIDE ACCESS TO BACKFLOW PREVENTOR. PROVIDE TEST. FS REQUIRES READY ACCESS PER 802.3.1
09/11/2013 BUILDING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/11/2013 BUILDING - FINAL Denied ICE MAKER NOT INSTALLED (TEMP ICE MAKER INSTALLED). SEPARATE CONDENSATE & BIN DRAINS. PROVIDE MIN 1" AG, ALSO, PROVIDE LISTED TUBING. ELECTRICAL DISCONNECT REQ. READY ACCESS. INSTALL COVERS ON ALL ELECTRICAL JUNCTION BOXES. FLOOR SINKS REQUIRE READY ACCESS. PROVIDE STERILIZER INSTALL INSTRUCTIONS; PROVIDE GRAVITY DRAINS W/ AIR GAPS. COMPLY W/ NOTES ON PO1; STERILIZE ALL NEW PIPING. VERIFY OR INSTALL SS009 PER PLAN NOTES AT ALL CARBONATORS. SUPPORT & PROVIDE 1" AIR GAP ON INDIRECT DRAINS - CASES.