Permit: T13CM02385

Parcel: 106041920


Addresses:

410 E MOHAVE RD

Inspection Status: Not ready for Inspection

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
07/22/2013 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/19/2013 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/09/2013 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
07/09/2013 ELECTRIC - FINAL Not ready for Inspection 1. ARC FAULT PROTECT ALL 15 OR 20 AMP CIRCUITS EXCEPT
GFCI CIRCUITS
2. EXISTING WIRING MIXED WITH NEW NOT PER PLAN - SUBMIT AS BUILT OR BUILD TO PLAN
3. GROUND METAL BOXES
4. ALL EXIT DOORS REQUIRE SWITCHED LIGHT FIXTURES
5. 12-2 WIRING ALL KITCHEN COUNTER OUTLETS - MISSING OUTLETS PER CODE
**WORK NOT COMPLETE ENOUGHT TO INSPECT - STOPPED INSPECTION**
04/23/2013 ELECTRIC - FINAL Not ready for Inspection 1. Have house rewire added to permit. Need to see branch circuitry connected to new panel/junction box.