Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/07/2013 | ELECTRIC - FINAL | Approved | REVIEW OF SYSTEM SHOWS THAT WHAT WAS BELIEVED TO BE A COMBINER BOX IS SIMPLY BEING USED AS A TRANSFER BOX. INVERTER WILL NOT WORK IF STRINGS ARE COMBINED AT THIS POINT. DISCUSSED WITH FIELD INSPECTOR AND GOT OK TO CLEAR. | |
| 09/03/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 09/03/2013 | ELECTRIC - FINAL | Denied | COMBINER ON ROOF NEEDS TO BE A LISTED UNIT - 690.4.D |