Inspection History Details
Inspection Status: Denied
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/22/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/22/2013 | ELECTRIC - FINAL | Denied | 1. WALKWAY LTG, NOT TO CODE (FRONT OUTSIDE) EXPOSED WIRING 2. INSTALL APPROVED BREAKER BLANKS IN SERVICE PANEL DEAD FRONT COVER 3. ROMEX & CORD CAP NOT TO CODE FOR KITCHEN -USE QUALIFIED OR LICENSED CONTR. TO MAKE REPAIRS. RESCH INSPECTION WHEN DONE. |