Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T13CM02311
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/10/2013 | FIRE - FINAL | Approved | FINAL | |
10/07/2013 | FIRE - FINAL | Partial Approval | OKAY TO STOCK No sales - No Public 1. 4 EM lights need repaired failed to work 2. Fire alarm system needs to be finshed 3. The sprinkler system tamper and flow switches for this property is already monitored by central alarm in the fire riser room, therefore for this new fire alarm system in suite #144 DOES NOT need to monitor the tamper or flow switches on the risers, but does need to be monitored. |