Permit: T13CM02236

Parcel: 132091610

Inspection Status: Approved

Inspection History: ELECTRIC - RECONNECT

Date Description Inspector Results Comments
05/03/2013 ELECTRIC - RECONNECT Approved IVRS - Inspection :*
05/01/2013 ELECTRIC - RECONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/01/2013 ELECTRIC - RECONNECT Denied -SMOKE DETETOR IN HALLWAY, AS PER NOTE #6 LAST INSPECTION.
-OTHER ITEMS OK.
04/17/2013 ELECTRIC - RECONNECT Not ready for Inspection IVRS - Inspection :*
04/17/2013 ELECTRIC - RECONNECT Not ready for Inspection 1) PLUG OPEN K.O. AT MAIN PANEL.
2) GROUND WIRE AT MAIN PANEL HAS BEEN CUT AND REMOVED NEEDS TO BE REPLACED WITH NEW WIRE AND GROUND ROD.
3) WHITE WIRE IS NOT TO BE USED AS HOT LEG (A/C0
4) ROMEX FROM REAR LIGHT OT SHED IS NOT TO CODE AND MUST BE REMOVED.
5) SEVERAL OUTLET AND SWITCH COVERS ARE BROKEN OR MISSING AND NEED TO BE REPLACED
6) SMOKE ALARM REQURED IN HALLWAY LEADING TO BEDROOM.