Permit: T13CM02221

Parcel: 13320004A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
12/06/2013 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
12/06/2013 PLUMBING - INTERMEDIATE Approved OK FOR INSULATION & SHEETROCK
11/27/2013 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/25/2013 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
11/22/2013 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
11/22/2013 PLUMBING - INTERMEDIATE Denied 1 1/4 WATER SUPPLY SHOWN W/ 1" SPLIT TO EACH END OF HOSE. SOFTENER IS NOT SHOWN. ADD DEVELOPED LENGTH. PROVIDE FULL SIZED PIPING THROUGH SOFTENER & SLIT. PROTECT PEX @ STUCCO. REMOVE METAL CLAMPS. SUPPORT AS REQUIRED. PROVIDE 18" AT COPPER SWEAT CONNECTIONS. INSULATION REQUIRED ON HW TO KITCHEN. WH REQ A DRAIN PAN. CPVC REQ PRIMER OR APPROVED CEMENT. PROVIDE CODE APPROVED PIPING SUPPORTS ON PEX, BLK STEEL, HOUSE VAC, & MECH OVERHEAD. VENT 90 AND HORIZONTAL OFFSET OF KIT VENT BELOW FLOOD LEVEL NOT ALLOWED. PIPE GAS INTO FACE PLATE & TEST. TEST DWV. INSP OF CLOSET FLANGE & SHOWER PAN LINER REQ WHEN READY.