Permit: T13CM02209

Parcel: 13405119H


Addresses:

9401 E 22ND ST


Inspection Status: Denied

Inspection History: ELECTRIC - INTERMEDIATE

Permit Number - T13CM02209

Inspection Description - ELECTRIC - INTERMEDIATE

Inspection Status - Denied

Date Description Inspector Results Comments
10/17/2013 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/17/2013 ELECTRIC - INTERMEDIATE Denied 1. LIGHTING INSTALLED AT CUSTOMER SERVICE OK
2. EXISTING LOW VOLTAGE & LIGHTING WHIPS & EMT TO BE REMOVED OR STRAPPED OFF GRID CEILING & ACCOUNTING ROOM
3. LIQUOR DEPARTMENT LIGHTING WHIPS & HOMERUN TO BE OFF GRID. J. BOX TO BE CLOSED UP & BEER COOLER TO BE CLEANED ON TOP
4. REDUCE AREA 1/2 K.O SEAL MISSING
5.BAKERY ARE3A LOW VOLTAGE TO BE OFF GRID
6. EXIT TO BE REMOUNTED BREAD AREA
7. LOW VOLTAGE & LLIGHTING WHIPS TO BE OFF GRID MEAT DEPARTMENT
8. SEAFOOD AREA OPEN J. BOXES & MC TO BE STRAPPED & OFF GRID
9. REFRIGERATION MC & J. BOXES TO BE STRAPPED AT CASES
10. DAIRY J. BOX OPEN. MC & LOW VOLTAGE TO BE STRAPPED
11. PHARMACY FLEX & LOW VOLTAGE TO BE OFF GRID
12. FRONT END 3/4 EMT & LOW COLTAGE TO BE STRAPPED & OFF GRID
13. PANELS AT BACKROOM. SPARES TO BE PLACED GOING INTO WALL & DOWN TO LIVE PANELS & WALL TO BE PATCHED
14. U.S CAN REGISTER 4 OPEN BOXES & LOW VOLTAGE TO BE OFF GRID
15. COVER MISSING FOR POWER STRIP
16. FRONT ENTRANCE STRIP LIGHTING 1/2 PLUG MISSING & BROKEN COVER
10/10/2013 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
10/10/2013 ELECTRIC - INTERMEDIATE Denied 1. COMMERCIAL KITCHEN OR PREP AREA TO BE GFI
2. IN CEILING J. BOX OPEN & K.O. SEAL MISSING
3. INDUSTRIAL COVERS TO HAVE 3 SCREWS
4. A/C SPLIT UNIT IN OFFICE OK - ROOF OK TOO
09/24/2013 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
09/24/2013 ELECTRIC - INTERMEDIATE Denied 1. CUSTOMER SERVICE MC TO BE STRAPPED & ABOVE CEILING - STILL TO BE INSPECTED
2. PRODUCE PREP TEE BAR - CEILING OK
3. ELECTRIC ABOVE CEILING AT PRODUCE PREP NOT READY
09/19/2013 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/12/2013 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
09/12/2013 ELECTRIC - INTERMEDIATE Partial Approval 1. ACCOUNTING ROOM OK
2. PRODUCE PREP ROOM ROUGH PLUMBING OK
3. STILL TO INSPECT ROOF A/C
08/29/2013 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/29/2013 ELECTRIC - INTERMEDIATE Partial Approval OUTLETS & LIGHTING IN ACCOUNTING ROOM
08/21/2013 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/21/2013 ELECTRIC - INTERMEDIATE Partial Approval NEW PANEL & TRANSFORMER SET IN PLACE
08/13/2013 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
08/13/2013 ELECTRIC - INTERMEDIATE Partial Approval FLORAL PREP AREA