Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/21/2013 | FIRE - FINAL | Approved | ||
| 10/28/2013 | FIRE - FINAL | Partial Approval | Okay to add fixtures and stock Need fire extinguishers post every 75 foot travel distance 2A-10BC type Need Sub to finish paying for the fire alarm permit T13BU01003 to clear it out. |
|
| 10/22/2013 | FIRE - FINAL | Denied | 1. Need alarm final called in 2 Need 5 year alarm valve inspection completed 3. Need to test back up lighting 20 min run time 4. Need fire extingushers posted 1 for every 1500 sq ft 75 foot travel distance - 2A-10BC type. |