Permit: T13CM02142

Parcel: 11904600L


Addresses:

502 W AJO WY #130


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T13CM02142

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
11/21/2013 FIRE - FINAL Approved
10/28/2013 FIRE - FINAL Partial Approval Okay to add fixtures and stock
Need fire extinguishers post every 75 foot travel distance 2A-10BC type
Need Sub to finish paying for the fire alarm permit T13BU01003 to clear it out.
10/22/2013 FIRE - FINAL Denied 1. Need alarm final called in
2 Need 5 year alarm valve inspection completed
3. Need to test back up lighting 20 min run time
4. Need fire extingushers posted 1 for every 1500 sq ft 75 foot travel distance - 2A-10BC type.