Inspection History Details
Inspection Status: Approved
Inspection History: FIRE SPKLR - FINAL
Permit Number - T13CM02142
Inspection Description - FIRE SPKLR - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
10/24/2013 | FIRE SPKLR - FINAL | Approved | ||
10/22/2013 | FIRE SPKLR - FINAL | Denied | 1. Correct upright sprinkler coverage remove all insulation from sprinkler heads need min 1 inch to max 12" inches from sprinkler heads at all times 2. Need spare heads in head box 3. Need fire alarm final called in 4. Need tamper switch installed on riser 5. Need 5 year alarm valve inspection completed |