Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/03/2013 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 07/02/2013 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 07/02/2013 | ELECTRIC - INTERMEDIATE | Denied | 1. USE APPROVED ROMEX CONNECTORS IN BOXES WITH CONCENTRIC KO'S 2. MC CABLE CANNOT TERMINATE INTO PLASTIC BOXES MADE FOR ROMEX 3. NAIL PLATES WHERE WIRING LESS THAN 1 1/4" FROM FACE OF STUD 4. SMOKE DETECTORS WIRING? 5. PLANS/PERMIT? |