Inspection History Details
Inspection Status: Partial Approval
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/12/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 04/12/2013 | ELECTRIC - FINAL | Partial Approval | 1. TIGHTEN SPLIT BOLT - MAIN PANEL 2. REMOVE GROUNDING ELECTRODE CONDUCTOR AT SUB PANEL 3. ONLY ONE NEUTRAL PER LUG TERMANATION 4. NEED LISTED MAST BRACE KIT 5. GROUND ROD ACORN CLAMP CONNECTED WRONG 6. PER INSPECTOR, 390-4533 NOT IN SERVICE *LEAVE OLD PAPERWORK ON SITE* |