Permit: T13CM01918

Parcel: 12801001B


Addresses:

240 S WILMOT RD

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
09/06/2013 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
09/06/2013 REINFORCED MASONRY PRE-GROUT Approved WALLS TOPPED-OUT AT 23' 8"; PILASTERS AT 4' 4" - OK TO GROUT PROGRESS AREAS
09/05/2013 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
09/05/2013 REINFORCED MASONRY PRE-GROUT Partial Approval EAST WALLS AT 21' - OK TO GROUT #4 VERTICAL BARS IN PLACE AT 32" ON CENTER
09/04/2013 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
09/04/2013 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALL AT 22' (TOP-OUT SOUTH WALL) WEST & NORTH WALL AT 21'
**NOTE:** SW WEST AREA ON WEST WALL - BOND BEAM PLACED FOLLOWING RACKED LEDGER NOT AS PER DETAIL #302, PAGE S601 (APPROX 25')
08/28/2013 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
08/28/2013 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 17'0" GL: 3/A.5-A.7; GL: 3/B.25-C; GL: C/1-3 (PILASTERS ONLY - 24" ABOVE LINTEL) - OK TO GROUT PROGRESS AREAS.
08/27/2013 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
08/27/2013 REINFORCED MASONRY PRE-GROUT Partial Approval CMU WALLS AT 17' GL: A/1-3; 3/C.5; GL: 1/A-C - OK TO GROUT PROGRESS AREAS D-6
08/22/2013 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
08/22/2013 REINFORCED MASONRY PRE-GROUT Partial Approval CONTINUOUS CMU WALLS AT 13' - OK TO GROUT PROGRESS AREAS
08/20/2013 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
08/20/2013 REINFORCED MASONRY PRE-GROUT Partial Approval CONTINUOUS CMU WALLS AT 4' 8" - 9' - OK TO GROUT PROGRESS AREAS
08/15/2013 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
08/15/2013 REINFORCED MASONRY PRE-GROUT Partial Approval STEM WALL (EAST WALL) GL: C/1.5-2, 2.25-2.5
ADDITONAL #8 REBAR IN EAST & WEST BEAM BEARING AREAS GL: 2/C, A/2 - OK TO GROUT PROGRESS AREAS
08/14/2013 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
08/14/2013 REINFORCED MASONRY PRE-GROUT Partial Approval CONTINUOUS CMU WALLS AT 0'-5' A.F.F.E. (EXCEPT FOR BEAM BEARING AREAS AT GL: 2/A & 2/C) (DETAIL #1, PAGE SO21)
OK TO GROUT PROGRESS AREAS