Permit: T13CM01909

Parcel: 117072590


Addresses:

720 S 2ND AV


Inspection Status: Approved

Inspection History: MECHANICAL - INTERMEDIATE

Permit Number - T13CM01909

Inspection Description - MECHANICAL - INTERMEDIATE

Inspection Status - Approved

Date Description Inspector Results Comments
05/29/2013 MECHANICAL - INTERMEDIATE Approved IVRS - Inspection :*
05/08/2013 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/08/2013 MECHANICAL - INTERMEDIATE Denied WORK IS NOT BEING COMPLETED, ANOTHER FAILED INSPECTION WILL RESULT IN THIS PERMIT BEING RE-FEE
05/03/2013 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
05/03/2013 MECHANICAL - INTERMEDIATE Denied 1. FLUE PIPE NOT PROPERLY INSTALLED
2. FLEX NOT PROPERLY SUPPORTED
3. FLEX DUCT WITHIN VENTED ATTIC - MUST BE MINIMUM R-8
4. LIGHT SWITCH TORE AT ADD'L ENTRANCE
04/30/2013 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/30/2013 MECHANICAL - INTERMEDIATE Not ready for Inspection CANCELLED PER OWNER
04/25/2013 MECHANICAL - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
04/18/2013 MECHANICAL - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
04/18/2013 MECHANICAL - INTERMEDIATE Not ready for Inspection -CATWALK AND PLATFORM NEEDED IN ATTIC
-SUPPORT CONDINSATE LINE