Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO. If you cannot find what you are looking for please submit a records request.

Permit: T13CM01881

Parcel: 126172680

Inspection Status: Approved

Inspection History: ELECTRIC - SERVICE UPGRADE

Date Description Inspector Results Comments
06/07/2013 ELECTRIC - SERVICE UPGRADE Approved IVRS - Inspection :*
06/05/2013 ELECTRIC - SERVICE UPGRADE Denied IVRS - Inspection :
See detailed listing on site.| 999*
06/05/2013 ELECTRIC - SERVICE UPGRADE Denied 1. GROUNDING ELECTRODE, WATER, & GAS BOND MISSING
2. SIZE SERVICE WIRES, PANEL HAS TEP LOCK
3. RISER BRACING TO BE LISTED & STRAPING TO BE REDONE