Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
Permit Number - T13CM01837
Inspection Description - FIRE - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
09/25/2013 | FIRE - FINAL | Approved | ||
09/18/2013 | FIRE - FINAL | Denied | - STILL NEED ITEMS #1 & #3 INSP - 9/13/13 - CASH WRAP NOT WIRED UP YET |
|
09/17/2013 | FIRE - FINAL | Denied | Tested all smoke duct detectors all passed. 1. Need to test the exits with delayed egress locks for the following: Doors unlock upon the actuation of the automatic sprinkler or fire alarm detection system. Unlock upon loss of power controlling the lock initiation of an irreversible process sign on door within 12 inches of release device reading PUSH UNTIL ALARM SOUNDS> DOOR CAN BE OPEN IN 15 (30) SECONDS Energency lighting shall be provided at the door 2. Insulation 1 inch plane above sprinkler heads in stock room. 3. 15 inch address numbers posted on building (handout given) |
|
09/16/2013 | FIRE - FINAL | Denied | Need Alarm permit finaled - T13BU00659 Need Sprinkler permit finaled - T13BU00585 Before calling in for frie finals |
|
09/13/2013 | FIRE - FINAL | Not ready for Inspection | 1. sprinkler placement ok. 2. insulation needs to be atleast one inch above sprinkler heads the entire ceiling not just around the sprinkler head. 3. need annual sprinkler report with no deficiencies and a five year check valve inspection, |