Permit: T13CM01837

Parcel: 11904600F


Addresses:

3781 S 12TH AV


Inspection Status: Approved

Inspection History: FIRE - FINAL

Permit Number - T13CM01837

Inspection Description - FIRE - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
09/25/2013 FIRE - FINAL Approved
09/18/2013 FIRE - FINAL Denied - STILL NEED ITEMS #1 & #3 INSP - 9/13/13
- CASH WRAP NOT WIRED UP YET
09/17/2013 FIRE - FINAL Denied Tested all smoke duct detectors all passed.
1. Need to test the exits with delayed egress locks for the following:
Doors unlock upon the actuation of the automatic sprinkler or fire alarm detection system.
Unlock upon loss of power controlling the lock
initiation of an irreversible process
sign on door within 12 inches of release device reading PUSH UNTIL ALARM SOUNDS> DOOR CAN BE OPEN IN 15 (30) SECONDS
Energency lighting shall be provided at the door

2. Insulation 1 inch plane above sprinkler heads in stock room.
3. 15 inch address numbers posted on building (handout given)
09/16/2013 FIRE - FINAL Denied Need Alarm permit finaled - T13BU00659
Need Sprinkler permit finaled - T13BU00585
Before calling in for frie finals
09/13/2013 FIRE - FINAL Not ready for Inspection 1. sprinkler placement ok.
2. insulation needs to be atleast one inch above sprinkler heads the entire ceiling not just around the sprinkler head.
3. need annual sprinkler report with no deficiencies and a five year check valve inspection,