Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date |
Description |
Inspector |
Results |
Comments |
| 12/18/2013 |
PLUMBING - SEWER HCS CONNECT |
|
Approved |
|
| 12/16/2013 |
PLUMBING - SEWER HCS CONNECT |
|
Partial Approval |
1. 4" combo reversed for test, not permitted. All drainage fittings to open in the direction of flow. 3" clean-out at lower end not big enough ffor 4" sewer. Electric not installed per plan. Gas not installed per plan. All changes to the plan must be approved. Minimum, accurate redlines at the time of the inspection. |