Inspection Status: Approved
Inspection History: FRAMING
| Date |
Description |
Inspector |
Results |
Comments |
| 05/19/2014 |
FRAMING |
|
Approved |
|
| 05/14/2014 |
FRAMING |
|
Partial Approval |
ADD STUDS UNDER DEN NORTH/SOUTH GLUELAM |
| 05/07/2014 |
FRAMING |
|
Not ready for Inspection |
1. Framing cant be approved until after plumbing, electrical, approvals. 2. ABS requires a water test. Vertical piping not supported. Overhead horizontal piping not supported. International codes do not recognize horizontal dry vent. (At upstairs water closet.) ABS shims not approved waste line support. 3. Under floor sleeve for gas at island does not meet code. 4. All mechanical registers to be supported on three sides. All drainage piping to have grade. Vertical X horizontal change of direction in waste piping to be a sweep. 5. Yardwater covered. |