Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - INTERMEDIATE
Permit Number - T13CM01810
Inspection Description - MECHANICAL - INTERMEDIATE
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/17/2013 | MECHANICAL - INTERMEDIATE | Approved | PER JIM 15 PSI TEST ON GAS LINE IS OK. PROVIDE MORE SUPPORT ON REFER LINE SET. DO NOT USE ZIP TIES FOR SUPPORT. OK TO SHEETROCK. |
|
| 06/12/2013 | MECHANICAL - INTERMEDIATE | Partial Approval | PER PH CALL | |
| 06/12/2013 | MECHANICAL - INTERMEDIATE | Partial Approval | PROVIDE A CONDENSATE DRAIN. T & P DRAIN DOES NOT FIT IN WALL. PROVIDE R-8 FLEX DUCT IN ATTIC. PROVIDE PLATE STRAPS AT DRYER VENT. GAS PRESSURE GAUGE NOT WORKING PROPERLY. PROVIDE BACKING AT CEILING BOXES. PROVIDE A/C LINE SET. OK TO INSULATE & SHEETROCK WALLS ONLY EXCEPT FOR PLUMBING WALL IN LAUNDRY ROOM. PROVIDE THE SLEEVE FOR FUTURE SOLAR AS PER PLANS. |