Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - UNDERGROUND
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2014 | ELECTRIC - UNDERGROUND | Approved | ||
| 08/19/2014 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 08/11/2014 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 08/11/2014 | ELECTRIC - UNDERGROUND | Denied | 24" MIN COVER UNDER FUEL DESPENSING CAOPY WHERE VEHICUALR TRAFFIC PER 300.5/514.8 NEC | |
| 08/01/2014 | ELECTRIC - UNDERGROUND | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 08/01/2014 | ELECTRIC - UNDERGROUND | Denied | U.G CONDUIT PVC BELOW FG FOR 514.8 NEC | |
| 07/11/2014 | ELECTRIC - UNDERGROUND | Partial Approval | IVRS - Inspection :* | |
| 07/11/2014 | ELECTRIC - UNDERGROUND | Partial Approval | - OKJ U.G TANK AREA ONLY |