Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T13CM01787
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/02/2014 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 09/30/2014 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 09/30/2014 | PLUMBING - FINAL | Denied | 1. DUCT SMOKE DETECTOR TEST REPORT OK 2. AIR BALANCE REPORT OK 3. COMPLETE W/H INSTALL, INSULATE ALL PIPING PER DETAIL 1-P1.3 4. TOILET NOT PROPERLY INSTALLED 5. TOILET SEAT COVER DISPENSOR NOT PROPERLY INSTALLED 6. EXHAUST GANS TO BE INTERLOCKED WITH RTU 7. ROOF TOP MATERIAL TO BE COATED FOR O.V PROTECTION |
|
| 09/26/2014 | PLUMBING - FINAL | Partial Approval | IVRS - Inspection :* 1. INSULATE DRAIN PIPES BATHS 2. PROVIDE BALANCE REPORT |