Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
PRO is currently experiencing an outage. Some documents and records may not be available on PRO momentarily. We apologize for the inconvenience and are working to restore full access.
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date |
Description |
Inspector |
Results |
Comments |
| 11/06/2013 |
PLUMBING - ROUGH, SOIL |
|
Approved |
|
| 09/24/2013 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
1. At meat island- ttwo floor sinks relocated OK. OK to cover. |
| 09/11/2013 |
PLUMBING - ROUGH, SOIL |
|
Partial Approval |
1. Two FD-4 on revised plan at Dairy Coolers OK. At Produce Prep. Drainage piping may only change direction forty five degrees without adding another clean-out. A blake tee is listed as a vertical surface wall clean-out. It is not a drainage fitting. It is not directional. Use directional fitting installed in the direction of flow. Reinspected: 2 floor drains at Produce OK. |