Permit: T13CM01786

Parcel: 10714376C


Addresses:

555 E GRANT RD

Inspection Status: Approved

Inspection History: PLUMBING - ROUGH, SOIL

Date Description Inspector Results Comments
11/06/2013 PLUMBING - ROUGH, SOIL Approved
09/24/2013 PLUMBING - ROUGH, SOIL Partial Approval 1. At meat island- ttwo floor sinks relocated OK. OK to cover.
09/11/2013 PLUMBING - ROUGH, SOIL Partial Approval 1. Two FD-4 on revised plan at Dairy Coolers OK. At Produce Prep. Drainage piping may only change direction forty five degrees without adding another clean-out. A blake tee is listed as a vertical surface wall clean-out. It is not a drainage fitting. It is not directional. Use directional fitting installed in the direction of flow. Reinspected: 2 floor drains at Produce OK.