Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - RECONNECT
Permit Number - T13CM01768
Inspection Description - ELECTRIC - RECONNECT
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 07/25/2013 | ELECTRIC - RECONNECT | Approved | IVRS - Inspection :* | |
| 03/28/2013 | ELECTRIC - RECONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. FRONT J.BOX AND LITE NOT WIRED TO CODE 245 AND FRONT J.BOX FOR LITING AND SIDE LITING ON EASTSIDE PIPE WITH WIRES TO REMOVED OK WIRED TO CODE TOO. 2. SERVICE PANEL DEAD FRONT AND 1/2 K.O SEAL ON BOTTOM OF PANEL MISSING 3. AC DISCONNECT ON ROOF MISSING COVER 4. LITES BEHIND HOUSE TO BE REWIRED AND ANCHORED AND J.BOX 5. GFI BEHIND HOUSE MISSING WEATHER PROOF COVER 6. GUEST HOUSE DISCONNECT WIRES ON BOTTOM TO BE CAPPED OR REMOVED 7. OUTLET FOR WEST BEDROOM TO BE ANCHORED TO WALL AND STRAPED 8. LIVING ROOM LITE J.BOX FOR LITE MISSING 9 EAST BEDROOM BROKEN OUTLET CLOSET J. BOX MISSING COVER |