Permit: T13CM01723

Parcel: 132171280

Inspection Status: Approved

Inspection History: FIRE - FINAL

Date Description Inspector Results Comments
05/16/2013 FIRE - FINAL Approved
05/14/2013 FIRE - FINAL Partial Approval Temp C of O approved to get final will need to following:
As stamped on front page of approved plans:
IFC 506.1 Key box needed for access to riser system, application let on site for key box.
IFC 903.4 & 903.4.1 monitoring - shall have sprinkler system monitored by an approved UL/FM company
05/13/2013 FIRE - FINAL Denied As stamped on front page of approved plans:
IFC 506.1 Key box needed for access to riser system, application let on site for key box.
IFC 903.4 & 903.4.1 monitoring - shall have sprinkler system monitored by an approved UL/FM company
05/07/2013 FIRE - FINAL Denied 1. Sprinkler permits still need to be finaled.
2. Remove keyed lock from ladder room door.
3. Sprinkler head in front office needs to be relocated. Cant be more than 7'6" off more than 1 wall.