Inspection History Details
Inspection Status: Approved
Inspection History: FIRE - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/16/2013 | FIRE - FINAL | Approved | ||
| 05/14/2013 | FIRE - FINAL | Partial Approval | Temp C of O approved to get final will need to following: As stamped on front page of approved plans: IFC 506.1 Key box needed for access to riser system, application let on site for key box. IFC 903.4 & 903.4.1 monitoring - shall have sprinkler system monitored by an approved UL/FM company |
|
| 05/13/2013 | FIRE - FINAL | Denied | As stamped on front page of approved plans: IFC 506.1 Key box needed for access to riser system, application let on site for key box. IFC 903.4 & 903.4.1 monitoring - shall have sprinkler system monitored by an approved UL/FM company |
|
| 05/07/2013 | FIRE - FINAL | Denied | 1. Sprinkler permits still need to be finaled. 2. Remove keyed lock from ladder room door. 3. Sprinkler head in front office needs to be relocated. Cant be more than 7'6" off more than 1 wall. |