Permit: T13CM01723

Parcel: 132171280

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
05/16/2013 FIRE SPKLR - FINAL Approved
05/14/2013 FIRE SPKLR - FINAL Denied As stamped on front page of approved plans:
IFC 506.1 Key box needed for access to riser system, application let on site for key box.
IFC 903.4 & 903.4.1 monitoring - shall have sprinkler system monitored by an approved UL/FM company
05/13/2013 FIRE SPKLR - FINAL Denied As stamped on front page of approved plans:
IFC 506.1 Key box needed for access to riser system, application let on site for key box.
IFC 903.4 & 903.4.1 monitoring - shall have sprinkler system monitored by an approved UL/FM company
05/03/2013 FIRE SPKLR - FINAL Denied 1. Sprinkler work done without permits.