Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING ABOVE CEILING
Permit Number - T13CM01592
Inspection Description - BUILDING ABOVE CEILING
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
05/28/2013 | BUILDING ABOVE CEILING | Approved | IVRS - Inspection :* | |
05/16/2013 | BUILDING ABOVE CEILING | Partial Approval | IVRS - Inspection :* | |
05/16/2013 | BUILDING ABOVE CEILING | Partial Approval | 1. FIRE ALARM CONDUIT AND BOX'S NEED TO BE RED IN COLOR. WORK NOT COMPLETE 2. COPPER LINES NOT TO BE IN CONTACT WITH DUCT WORK 3. DUCT NOT COMPLETE OR SEALED OR PROPERLY STRAPPED ECT... |