Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/15/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/09/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 05/09/2013 | ELECTRIC - FINAL | Denied | SUB PANEL: 1. SHEET METAL INTO WOOD NOT CORRECT HARDWARE #10 MINIMUM 2. FINISH #3 (408.4) MAIN PANEL: 1. FINISH #3 & 6 |
|
| 05/07/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 05/07/2013 | ELECTRIC - FINAL | Denied | SUB PANEL: 1. ONLY ONE NEUTRAL CONDUCTOR TO TERMINAL LUGS 2. USE APPROVED HARDWARE FOR MOUNTING - NOT DRY WALL SCREWS 3. LABEL CIRCUITS PER 408.4 MAIN PANEL: 1. LOCKNUT INSTALLED BACKWARDS 2. PROJECT CONDUCTORS FROM SHARP METAL EDGES. 300.4 3. MARKING TAPE TO ENCIRCLE CONDUCTOR 4. STRAP GROUNDING ELECTRODE CONDUCTOR TO STRUCTURE 5. MAINTAIN WIRE BENDING RADIUS 6. NEED GAS & WATER BONDING |