Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - FINAL
Permit Number - T13CM01506
Inspection Description - PLUMBING - FINAL
Inspection Status - Approved
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/22/2013 | PLUMBING - FINAL | Approved | IVRS - Inspection :* | |
| 03/19/2013 | PLUMBING - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 03/18/2013 | PLUMBING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* SYSTEM NOT HOLDING PRESSURE. PROVIDE A MIN. 10LB TEST. CANNOT OPEN LOCK BOX. NEED ACCESS INSIDE HOUSE. REPLACE T AND P VALVE ON WATER HEATER. DRAFT DIVERTER AND VENT ON WATER WATER NEEDS TO BE FASTENED BETTER AND SCREWED TO TOP OF WATER HEATER. THE ELECTRICAL BOND TO WATER PIPING AT THE LAUNDRY FAUCET NEEDS TO BE ON THE COLD WATER PIPE, TIGHTENED, AND THEN JUMPERED TO THE GAS PIPE. PROVIDE ACCESS TO THE FURNACE ON ROOF. |