Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/09/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/04/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection :NOTES 2,3,4,AND 5 FROM PREVIOUS | |
| 03/15/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) UNABLE TO VERIFY PANEL GROUNDING 2) WHITE 60 AMP HOT LEAD TO BE RED OR BLACK (TAPE OK) 3) SEAL KNOCKOUT BOTTOM PANEL 4) CONSULT WITH TEP ON DROP 24" FROM PORCH ADDITION. PROVIDE RESULTS 5) PROVIDE ACCESS REAR STORAGE 6) PROTECT EXPOSED ROMEX THROUGHOUT INTERIOR FROM PHYSICAL DAMAGE 7) SMOKE ALARM BEDROOMS AND HALLWAYS 8) 2 WIRE OUTLETS AND GROUNDED OUTLETS MIXED THROUGHOUT. 9) ALL ADDITIONS SHOULD BE ON RECORD 10) WATER HEATER NOT MAINTAINED IN SAFE CONDITION NOTES 1-8 FOR POWER. |