Permit: T13CM01496

Parcel: 138141390


Addresses:

101 W BILBY RD


Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Permit Number - T13CM01496

Inspection Description - ELECTRIC - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
04/09/2013 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/04/2013 ELECTRIC - FINAL Denied IVRS - Inspection :NOTES 2,3,4,AND 5 FROM PREVIOUS
03/15/2013 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) UNABLE TO VERIFY PANEL GROUNDING
2) WHITE 60 AMP HOT LEAD TO BE RED OR BLACK (TAPE OK)
3) SEAL KNOCKOUT BOTTOM PANEL
4) CONSULT WITH TEP ON DROP 24" FROM PORCH ADDITION. PROVIDE RESULTS
5) PROVIDE ACCESS REAR STORAGE
6) PROTECT EXPOSED ROMEX THROUGHOUT INTERIOR FROM PHYSICAL DAMAGE
7) SMOKE ALARM BEDROOMS AND HALLWAYS
8) 2 WIRE OUTLETS AND GROUNDED OUTLETS MIXED THROUGHOUT.
9) ALL ADDITIONS SHOULD BE ON RECORD
10) WATER HEATER NOT MAINTAINED IN SAFE CONDITION NOTES 1-8 FOR POWER.