Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/12/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/30/2013 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/15/2013 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 04/12/2013 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/12/2013 | ELECTRIC - FINAL | Denied | 1. NEED FEILD EVALUATION FOR MODIFICATION OF SERVICE EQUIPMENT - ROUND BOLTS INSQUARE HOLE 2. MAINTAIN WORKING SPACE JOCKEY PUMP CONTROLLER 110.26 3. BOND MYERIS HUB BUSHING 250.92 4. SEAL UNUSED JUNCTION BOX OPENINGS 5. LOOSE FITTINGS LIGHT SWITCH BOX 6. LIGHTS NOT INSTALLED 7. ARE THERE PLANS FOR STRUCTURE? *PLANS DO NOT SHOW ROOM OR LIGHTING* |