Permit: T13CM01142

Parcel: 12405007B


Addresses:

825 E UNIVERSITY BL

Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Date Description Inspector Results Comments
08/06/2013 FIRE SPKLR - FINAL Approved
07/22/2013 FIRE SPKLR - FINAL Denied 1. Display case windows in front of buiilding shall have sprinkler coverage added.
2. Correct sprinlker coverage back storage room by ladder to roof 2 heads one on each side of ladder are blocked by 1 1/2 angle iron truss.
3. As per approved plans correct sprinkler coverage add upright by mechanical room wall.
4. Will need a key box install on the riser room door for acess and label door "RISER ROOM".
5. Need anunal sprinkler report (4/13/2012) pass due.
6. Need 5 year check valve inspection done pass due (4/2001)