Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/03/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/02/2013 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 05/02/2013 | ELECTRIC - FINAL | Partial Approval | 1) ALL KITCHEN REEPTACLES TO BE GFCI PROTECTED 210.8 (B) 2) COMMERCIAL DISHWASHER WET LOCATION 406.8 3) NEED DISCONNECTING MEANS WALK IN CONDENSOR 4) BATHROOM EM LIGHT TO BE ON CIRCUIT SERVICED 700/12(F) AND LOBBY 5) NEED EXTERIOR EM LIGHTS 6) NEED CLORINATION REPORT REVIEWD AIR BALANCE REPORT |