Permit: T13CM01083

Parcel: 116126300

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/03/2013 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/02/2013 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
05/02/2013 ELECTRIC - FINAL Partial Approval 1) ALL KITCHEN REEPTACLES TO BE GFCI PROTECTED 210.8 (B)
2) COMMERCIAL DISHWASHER WET LOCATION 406.8
3) NEED DISCONNECTING MEANS WALK IN CONDENSOR
4) BATHROOM EM LIGHT TO BE ON CIRCUIT SERVICED 700/12(F) AND LOBBY
5) NEED EXTERIOR EM LIGHTS
6) NEED CLORINATION REPORT
REVIEWD AIR BALANCE REPORT