Permit: T13CM00975

Parcel: 14041009A


Addresses:

3350 E VALENCIA RD


Inspection Status: Approved

Inspection History: FIRE SPKLR - FINAL

Permit Number - T13CM00975

Inspection Description - FIRE SPKLR - FINAL

Inspection Status - Approved

Date Description Inspector Results Comments
03/13/2014 FIRE SPKLR - FINAL Approved
10/16/2013 FIRE SPKLR - FINAL Denied 1. Analytical Lab shower need sprinkler coverage X2
2. Chem storage room correct coverage 8' 6" off wall
3. Mineralogy - high grade room correct sprinkler coverage 8' 6" off wall
4. Mineralogy - Mid grade room correct sprinkler coverage 8' 6" off wall
5. In corridor (on plans S-46 next to personnel space, submittal office, supervisor office) correct sprinkler coverage
6. Mineralogy north correct sprinkler coverage in shower
7. East corridor area C (by Qemscam rm, Util Chase rm, XRD Lab rm) correct sprinkler coverage heads 20' feet apart
8. Hydro test all new piping installed for the dry system for 2 hours at 200 PSI.
09/13/2013 FIRE SPKLR - FINAL Partial Approval 1. ok to occupy phase one only.
2. sprinkler placemet is ok in phase one water flow was tested and passed tampers not online although they are chained open.
3. move handicap sign away from fdc
4. emergency lights tested and passed in phase one