Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/20/2013 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 02/20/2013 | ELECTRIC - FINAL | Denied | REMOVE RECEPTACLE AT CARPORT OR WIRE PER CODE. ANY OUTDOOR RECEPTACLE MUST BE GFI AND WEATHER PROOF REPAIR BROKEN CONDUIT AT POOL EQUIPMENT REMOVE THE CORD AND PLUG OUTDOOR LIGHTS SEAL OPEN KNOCKOUT IN DISCONNECT AT A/C UNIT REPLACE ANY BROKEN RECEPTACLE SMOKE DETECTORS REQUIRED IN EACH BEDROOM AND I OUTSIDE OF BEDROOMS |