Inspection History Details
Inspection Status: Approved
Inspection History: BUILDING - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/06/2014 | BUILDING - FINAL | Approved | IVRS - Inspection :* | |
| 05/09/2014 | BUILDING - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 05/09/2014 | BUILDING - FINAL | Denied | 1. TO SEE BREAKER INSTALLED - LOCATION OK 2. GROUNDING ELECTRODE TO BE #8 & BOND BUSHING MISSING 3. NEUTRAL TO PASS STRAIGHT THRU NOT TO BE BONDED AT METER BASE 4. BREAKER LABELS MISSING 5. ON ROOF SOLAR PANEL WIRES TO INVERTER TO BE PROTECTED FROM PHYSICAL DAMAGE |